Description:

Inspection

Outstanding Inspections

Case Number: T09FR03225
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
10/07/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extention cord located at the west exit shall not be used in place of permanent wiring. The cord shall not be subject to physical damage or run under floor coverings.
10/07/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The portable fire extinguisher shall be inspected annually.
10/07/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 The portable fire extinguisher shall be mounted on hanger.
10/07/2009 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required 2604.1.1 The hot work area shall not contain combustibles.
10/07/2009 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required 2604.2.6 A 2A:20BC rated portable fire extinguisher shall be provided for the hot work area.
10/07/2009 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required 2609.2 The hose for the propane gas shall be protected from physical damage.
10/07/2009 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5 NFPA 704 hazard identification signs shall be posted at the front and rear exits.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03225
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/04/2009 INSP - FULL TKNAPP Approved