Case: T09FR03225
Case Details
Entered Date:
10/07/2009
Applicant:
KOLVOORD FAMILY LTD PARTNERSHIP
Description:
Inspection
Outstanding Inspections
Case Number: T09FR03225
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The extention cord located at the west exit shall not be used in place of permanent wiring. The cord shall not be subject to physical damage or run under floor coverings. |
10/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguisher shall be inspected annually. |
10/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 The portable fire extinguisher shall be mounted on hanger. |
10/07/2009 | VIOL - WELDING & OTHER HOT WRK | TKNAPP | Correction Required | 2604.1.1 The hot work area shall not contain combustibles. |
10/07/2009 | VIOL - WELDING & OTHER HOT WRK | TKNAPP | Correction Required | 2604.2.6 A 2A:20BC rated portable fire extinguisher shall be provided for the hot work area. |
10/07/2009 | VIOL - WELDING & OTHER HOT WRK | TKNAPP | Correction Required | 2609.2 The hose for the propane gas shall be protected from physical damage. |
10/07/2009 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5 NFPA 704 hazard identification signs shall be posted at the front and rear exits. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03225
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2009 | INSP - FULL | TKNAPP | Approved |