Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/22/2009

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full Fire Prevention Inspection. Angela Contreras 903-1571

Outstanding Inspections

Case Number: T09FR03083
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/22/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____1. Remove all storage from obstructing the sprinkler system riser and control valves located in the east stock room.
09/22/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____1. Replace the missing portable fire extinguisher located in the 2nd floor west side storage area.
09/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. The exit sign located above the northeast exit door shall be internally illuminated. _____2. The west exit sign shall be internally illuminated.
09/22/2009 VIOL - HIGH PILED COMBUSTIBLES JBURGE Correction Required IFC 2305.4 Aisle maintenance. When restocking is not being conducted, aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained in 48-inch (1219 mm) or smaller aisles, and a minimum unobstructed aisle width of one-half of the required aisle width shall be maintained in aisles greater than 48 inches (1219 mm). _____1. Maintain the required clear isle space in the lower East storage room.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03083
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/13/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.