Case: T09FR03083

Parcel: 11618432G

Inspection Status: Correction Required

Inspection History: VIOL - HIGH PILED COMBUSTIBLES

Case Number - T09FR03083

Inspection Description - VIOL - HIGH PILED COMBUSTIBLES

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/22/2009 VIOL - HIGH PILED COMBUSTIBLES Correction Required IFC 2305.4 Aisle maintenance. When restocking is not being conducted,
aisles shall be kept clear of storage, waste material and
debris. Fire department access doors, aisles and exit doors shall
not be obstructed. During restocking operations using manual
stocking methods, a minimum unobstructed aisle width of 24
inches (610 mm) shall be maintained in 48-inch (1219 mm) or
smaller aisles, and a minimum unobstructed aisle width of
one-half of the required aisle width shall be maintained in
aisles greater than 48 inches (1219 mm).

_____1. Maintain the required clear isle space in the lower East storage room.