Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

09/15/2009

Applicant:

DECAGEE LLC

Description:

inspection

Outstanding Inspections

Case Number: T09FR03025
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
09/15/2009 INSP - FULL EGRIFFIN Violation 1).The automatic fire sprinkler system mall is violation of the following. IFC 901.6 A). Main shut off valve requires electronic supervision or lock. B). Check requires 5 year inspection. C). Repair and replace main valve, currently it does not fully close. D). An assortment of spare sprinkler heads shall be furnished.. E). Always keep sprinkler riser room unobstructed.