09/15/2009 INSP - FULL Violation 1).The automatic fire sprinkler system mall is violation of the following. IFC 901.6
A). Main shut off valve requires electronic supervision or lock.
B). Check requires 5 year inspection.
C). Repair and replace main valve, currently it does not fully close.
D). An assortment of spare sprinkler heads shall be furnished..
E). Always keep sprinkler riser room unobstructed.