Case: T09FR02980
Case Details
Entered Date:
09/14/2009
Applicant:
SMITH FAMILY REAL ESTATE INVESTORS LTD
Description:
Initial inspection 9/14/09
Outstanding Inspections
Case Number: T09FR02980
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2009 | VIOL - ADMINISTRATION | MPURSLEY | Correction Required | 105.6.16 Flammable and combustible liquids. An operational permit is required to store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. _____Have tanks permitted. |
09/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips |
09/14/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPURSLEY | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. |
09/14/2009 | VIOL - FLAMMABLE LIQUIDS | MPURSLEY | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30. _____Have tanks properly vented with atmospheric and emergency vents. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02980
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2009 | INSP - REINSPECTION | MPursley | Approved | All corrections made and tanks permitted, 11/10/09. |