Description:

Initial inspection 9/14/09

Outstanding Inspections

Case Number: T09FR02980
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/14/2009 VIOL - ADMINISTRATION MPURSLEY Correction Required 105.6.16 Flammable and combustible liquids. An operational permit is required to store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. _____Have tanks permitted.
09/14/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips
09/14/2009 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Non required fire protection systems and equipment shall be inspected, tested and maintained or removed.
09/14/2009 VIOL - FLAMMABLE LIQUIDS MPURSLEY Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30. _____Have tanks properly vented with atmospheric and emergency vents.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02980
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/10/2009 INSP - REINSPECTION MPursley Approved All corrections made and tanks permitted, 11/10/09.