Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE LIQUIDS
Case Number - T09FR02980
Inspection Description - VIOL - FLAMMABLE LIQUIDS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2009 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30. _____Have tanks properly vented with atmospheric and emergency vents. |