Case: T09FR02980

Parcel: 13327001C


Addresses:

7950 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE LIQUIDS

Case Number - T09FR02980

Inspection Description - VIOL - FLAMMABLE LIQUIDS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/14/2009 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure
caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30.
_____Have tanks properly vented with atmospheric and emergency vents.