Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR02740
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
08/24/2009 VIOL - PRECAUTION AGAINST FIRE MWAINWRI Violation 2006 IFC 304.1 REMOVE ITEMS LEADING TO AND AROUND GAS METER AND SHUT OF VALVE.
08/24/2009 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.1 OUTLET COVER PLATE FOR SWITCHES FOR SHOP LIGHTS
08/24/2009 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation 2006 IFC 703.1 REPLACE MISSING CEILING TILE IN LUNCHROOM (SERVICE)
08/24/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE FIRE EXTINGUISHER IN PARTS BY EXIT DOOR UPPER PARTS BY STAIRWAY SHOP BY JASONS BOOTH LUNCH ROOM STEVENS BAY WILEY STEVANS BAY WILEYS BAY LEO BAY STEVES BAY KEVINS BAY CARLOS BAY KIPS BAY BODY ONE BY BATHROOM BODY TWO BODY THREE BODY SHOP OFFICE USED CAR BUILDING WIATING ROOM 2 SALES WAITING ROOM SERVICE AND TAG SHOP SPRINKLER SYSTEM SERVICE AND TAG SPRINKLER SYSTEM FOR SPRAY BOOTH SERVICE AND TAG SPRINKLER SYSTEM FOR SHOWROOM
08/24/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 REPAIR EXIT SIGN BY PARTS COUNTER
08/24/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 REPAIR EMERGENCY LIGHTS IN SERVICE WAITING ROOM USED CAR BUILDING WAITING ROOM (2) TRAING ROOM UPSTAIRS 2 BUSINESS OFFICE UPPER HALLWAY 3
08/24/2009 VIOL - FLAMMABLE LIQUIDS MWAINWRI Violation 2006 IFC 3403.5 LABEL THE WASTE OIL TANK OUTSIDE "USED OIL"
08/24/2009 VIOL - FLAMMABLE LIQUIDS MWAINWRI Violation 2006 IFC 3404.3.1.1 THE WASTE OIL STORAGE TANK IN THE SHOP NEDS TO BE AN APPROVED UL LISTED TANK WITH EMERGENCY VENTS AND NORMAL VENT.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02740
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/02/2010 INSP - FULL WMOTTO Approved COMPLETED REINSPECTION ALL VIOLATIONS CORRECTED.