Addresses:

3566 E SPEEDWAY BL


Inspection Status: Violation

Inspection History: VIOL - FLAMMABLE LIQUIDS

Case Number - T09FR02740

Inspection Description - VIOL - FLAMMABLE LIQUIDS

Inspection Status - Violation

Date Description Inspector Results Comments
08/24/2009 VIOL - FLAMMABLE LIQUIDS Violation 2006 IFC 3404.3.1.1
THE WASTE OIL STORAGE TANK IN THE SHOP NEDS TO BE AN APPROVED UL LISTED TANK WITH EMERGENCY VENTS AND NORMAL VENT.
08/24/2009 VIOL - FLAMMABLE LIQUIDS Violation 2006 IFC 3403.5
LABEL THE WASTE OIL TANK OUTSIDE "USED OIL"