Case: T09FR02590
Case Details
Entered Date:
08/04/2009
Applicant:
1031 HOLDER LLC
Description:
Full Fire Prevention Inspection. Davinder Singh 292-1738
Outstanding Inspections
Case Number: T09FR02590
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.5.1 Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. _____1. The power-stip used to power the OPEN sign shall be plugged directly into an elecrtical outlet. |
| 08/04/2009 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____1. Replace the missing ceiling tiles located above the north exit door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 08/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. _____1. Provide a copy of the hood extinguishing system inspection report. _____2. Service and test the fire alarm system and provide a copy of the inspection report. |
| 08/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the hood system and provide documentation of the cleaning. |
| 08/04/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair the emergency lighting unit located on the wall by the north exit door. |
| 08/04/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove all storage from obstructing the north exit access and exit door. |
| 08/04/2009 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following method. _____1. Secure the CO2 cylinders located in the kitchen to a fixed object with one or more restraints. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02590
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |