Case: T09FR02590

Parcel: 10603100C

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR02590

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/04/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6.2 Records. Records of all system inspections, tests and
maintenance required by the referenced standards shall be
maintained on the premises for a minimum of three years and
shall be copied to the fire code official upon request.

_____1. Provide a copy of the hood extinguishing system inspection report.

_____2. Service and test the fire alarm system and provide a copy of the inspection report.
08/04/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

_____1. Clean and remove all grease accumulation from the hood system and provide documentation of the cleaning.