Case: T09FR02537
Case Details
Entered Date:
07/30/2009
Applicant:
WEST MAIN GATE CENTER LLC
Description:
SPRINKLER COMPLAINT
Outstanding Inspections
Case Number: T09FR02537
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | INSP - FULL | EDESCHAI | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE 1) ZWIRL - THE PAINTED SPRINKLER HEAD ABOVE THE SERVING COUNTER SHALL BE CHANGED OUT 2) THE PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE CHANGED OUT OR CALIBRATED 3) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE |