Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR02537
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE 1) ZWIRL - THE PAINTED SPRINKLER HEAD ABOVE THE SERVING COUNTER SHALL BE CHANGED OUT 2) THE PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE CHANGED OUT OR CALIBRATED 3) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE |