Case: T09FR02537

Parcel: 12405007B


Addresses:

825 E UNIVERSITY BL

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/30/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE

1) ZWIRL - THE PAINTED SPRINKLER HEAD ABOVE THE SERVING COUNTER SHALL BE CHANGED OUT

2) THE PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE CHANGED OUT OR CALIBRATED

3) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE