Case: T09FR02535
Case Details
Entered Date:
07/30/2009
Applicant:
WEST MAIN GATE CENTER LLC
Description:
SPRINKLER COMPLAINT
Outstanding Inspections
Case Number: T09FR02535
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | INSP - FULL | EDESCHAI | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE REPAIRED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE 1) SPRING NAIL SALON - THE PAINTED QUICK RESPONSE SPRINKLER HEAD IN THE STORE ROOM SHALL BE REPLACED 2) PEI WEI - ALL RECESSED SPRINKLER HEADS SHALL HAVE THE MISSING RECESSED STYLE ESCUTCHEONS MISSING SHALL HAVE THEM REPLACED 3) PITA PIT - RECESSED SPRINKLER HEAD ESCUTCHEONS THAT ARE MISSING SHALL BE REPLACED ( 2 PLACES) 4) PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE REPLACED OR CALIBRATED 5) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE |