Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR02437
Case Details
Entered Date:
07/23/2009
Applicant:
845 E OHIO LLC
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T09FR02437
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2009 | INSP - FULL | JNAGORE | Violation | 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the requiredwidth of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. Maintain exit pathways throughout the building. Maintain isle ways. |
07/23/2009 | INSP - FULL | JNAGORE | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. |
07/23/2009 | INSP - FULL | JNAGORE | Violation | 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. Make sure all exit lights are illuminated. |
07/23/2009 | INSP - FULL | JNAGORE | Violation | 315.2.2 Means of egress. Combustible materials shall not be stored in exits or exit enclosures. |
07/23/2009 | INSP - FULL | JNAGORE | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. do not block panels. |
07/23/2009 | INSP - FULL | JNAGORE | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Service extinguishers. |