Case: T09FR02437

Parcel: 132166160


Addresses:

845 E OHIO ST


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR02437

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
07/23/2009 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
do not block panels.
07/23/2009 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
Service extinguishers.
07/23/2009 INSP - FULL Violation 1003.6 Means of egress continuity. The path of egress travel
along a means of egress shall not be interrupted by any building
element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the requiredwidth of a means of egress except projections permitted by this
chapter. The required capacity of a means of egress system
shall not be diminished along the path of egress travel.
Maintain exit pathways throughout the building. Maintain isle ways.
07/23/2009 INSP - FULL Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.
07/23/2009 INSP - FULL Violation 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.
Make sure all exit lights are illuminated.
07/23/2009 INSP - FULL Violation 315.2.2 Means of egress. Combustible materials shall not
be stored in exits or exit enclosures.