Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR02394
Case Details
Entered Date:
07/20/2009
Applicant:
DUFFY WAREHOUSES LLC
Description:
FIRE SPRINKLER SYSTEM COMPLAINT
Outstanding Inspections
Case Number: T09FR02394
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | RHEATH | Violation | An open junction box in STE 3A. Provide the proper cover. TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Robert Heath, INSPECTOR TUCSON FIRE DEPARTMENT PROPERTY REPRESENTATIVE |
| 07/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | RHEATH | Violation | A 6' X 10' room was errected inside suite 3A without providing sprinkler protection. Install sprinklers in the room or remove the ceiling. TFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. |
| 07/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | RHEATH | Violation | The sprinkler system was last inspected in 2003. Have your sprinkler system serviced in accordance with NFPA Standard 25. TUCSON FIRE CODE (TFC) 901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02394
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2009 | INSP - FULL | RHEATH | Approved | A re-inspection was conducted today: Sprinkler serviced 7/28/2009; in FULL COMPLIANCE. Junction cox cover replaced and the roof was removed from the 6 X 10 space. CLOSED! |