Case: T09FR02394

Parcel: 13213063A


Addresses:

3640 S CAMPBELL AV


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR02394

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/20/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required Records indicate that the fire sprinkler system is overdue its annual inspection/ servicing.
07/20/2009 VIOL - FIRE PROTECTION SYSTEMS Violation A 6' X 10' room was errected inside suite 3A without providing sprinkler protection. Install sprinklers in the room or remove the ceiling. TFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection
whenever the building is altered, remodeled or added to. Alterations
to fire protection systems shall be done in accordance with applicable standards.
07/20/2009 VIOL - FIRE PROTECTION SYSTEMS Violation The sprinkler system was last inspected in 2003. Have your sprinkler system serviced in accordance with NFPA Standard 25. TUCSON FIRE CODE (TFC) 901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards.