Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR02394
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Records indicate that the fire sprinkler system is overdue its annual inspection/ servicing. | |
| 07/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | A 6' X 10' room was errected inside suite 3A without providing sprinkler protection. Install sprinklers in the room or remove the ceiling. TFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. |
|
| 07/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | The sprinkler system was last inspected in 2003. Have your sprinkler system serviced in accordance with NFPA Standard 25. TUCSON FIRE CODE (TFC) 901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards. |