Outstanding Inspections
Case Number: T09FR02192
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2009 | INSP - FULL | EDESCHAI | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR ORDER SHALL BE FORWARDED TO THIS OFFICE 1) GUAGES ARE DUE FOR REPLACEMENT OR CALIBRATION 2) THE ALARM VALVE IS DUE FOR THE 5 YEAR INTERNAL INSPECTION 3) TW0 (2) 165 DEGREE SIDEWALL SPRINKLERS TO BE ADDED TO THE HEAD BOX. 4) SPRINKLERS THAT ARE DAMAGED, CORRODED, PAINTED OR LEAKING SHALL BE CHANGED OUT. |