Case: T09FR02068
Case Details
Entered Date:
06/29/2009
Applicant:
ENCHANTED HILLS BAPTIST CHURCH INC
Description:
Enchanted Hills Baptist Church fire inspection.
Outstanding Inspections
Case Number: T09FR02068
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - REINSPECTION | None | Not Inspected | ||
06/29/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler inspection report. |
06/29/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.6.2 Grease extractors. Where grease extractors are installed, they shall be operated when the commercial- type cooking equipment is used. |
06/29/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ___Eliminate locking bolts from exit door at fellowshiphall , provide exit signage and appropriate opening handles. |
06/29/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.5 Unlatching. The unlatching of any leaf shall not require more than one operation. |
06/29/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ___Eliminate exit sign going into fellowship hall and redirect exit arrows towards exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02068
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346. |