Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR02068
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2009 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8.5 Unlatching. The unlatching of any leaf shall not require more than one operation. | |
06/29/2009 | VIOL - MEANS OF EGRESS | Violation | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ___Eliminate exit sign going into fellowship hall and redirect exit arrows towards exit. |
|
06/29/2009 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ___Eliminate locking bolts from exit door at fellowshiphall , provide exit signage and appropriate opening handles. |