Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/25/2009

Applicant:

KUHLMANN ROBERT & JILL JT/RS

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T09FR02057
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
06/25/2009 INSP - FULL JNAGORE Violation 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Do not block electrical panels.
06/25/2009 INSP - FULL JNAGORE Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 605.5.1 Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. 605.5.2 Ampacity. The ampacity of the extension cords shall not be less than the rated capacity of the portable appliance supplied by the cord. 605.5.3 Maintenance. Extension cords shall be maintained in good condition without splices, deterioration or damage. 605.5.4 Grounding. Extension cords shall be grounded when serving grounded portable appliances. 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Do not use extension cords.