Case: T09FR02057

Parcel: 129043230


Addresses:

435 S NORRIS AV


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR02057

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
06/25/2009 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Do not block electrical panels.
06/25/2009 INSP - FULL Violation 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
605.5.1 Power supply. Extension cords shall be plugged
directly into an approved receptacle, power tap or multiplug
adapter and, except for approved multiplug extension cords,
shall serve only one portable appliance.
605.5.2 Ampacity. The ampacity of the extension cords
shall not be less than the rated capacity of the portable appliance
supplied by the cord.
605.5.3 Maintenance. Extension cords shall be maintained
in good condition without splices, deterioration or damage.
605.5.4 Grounding. Extension cords shall be grounded
when serving grounded portable appliances.
605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.
Do not use extension cords.