Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/19/2009

Applicant:

SEC PLAZA PALOMINO LLC 89% & NEW RUDASILL LA

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR02003
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/19/2009 VIOL - FIRE SERVICE FEATURES MWAINWRI Violation 2006 IFC 506.1 INSTALL A FIRE DEPT LOCK ON THE NEW DOUBLE GATE FOR ACCESS DURING AFTER HOURS.
06/19/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE AND TAG SPRINKLER SYSTEM ON NORTH BUILDING. SERVICE AND TAG FIRE EXTINGUISHERS IN EACH ELEVATOR ROOM.
06/19/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 REPAIR THE EXIT SIGNS BY THE SOUTH AND NORTH GATES ON THE NORTH BUILDING
06/19/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 ON THE NORTH BUILDING AN EMERGENCY LIGHT NEEDS TO BE INSTALLED ON THE OUTSIDE STAIRS IN SUITE 209
06/19/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1028.2 ON THE NORTH BUILDING THE 2 SINGLE EGRESS GATES ON TEH SOUTH AND NORTH SIDE SHALL HAVE THE CANE BOLT REMOVED. THIS GATE USES AN EMERGENCY LEVER AND CANNOT HAVE ANY LOCKING MECHANISMS INSTALLED ON THE GATE.
06/19/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1028.2 REPAIR STAIRS ON NORTH BUILDING ON FAR EAST END FROM 3RD FLOOR TO GROUND FLOOR. THE STAIRS ARE CURRENTLY UNSAFE ACCORDING TO AN ARCHITECT AND ARE BLOCKED.
06/19/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation REPAIR THE EMERGENCY LIGHTS BY THE SOUTH AND NORTH GATES ON THE NORTH BUILDING