Case: T09FR02003

Parcel: 11005014C


Addresses:

2950 N SWAN RD


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR02003

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
06/19/2009 VIOL - MEANS OF EGRESS Violation 2006 IFC 1027.5
ON THE NORTH BUILDING AN EMERGENCY LIGHT NEEDS TO BE INSTALLED ON THE OUTSIDE STAIRS IN SUITE 209
06/19/2009 VIOL - MEANS OF EGRESS Violation 2006 IFC 1028.2
ON THE NORTH BUILDING THE 2 SINGLE EGRESS GATES ON TEH SOUTH AND NORTH SIDE SHALL HAVE THE CANE BOLT REMOVED. THIS GATE USES AN EMERGENCY LEVER AND CANNOT HAVE ANY LOCKING MECHANISMS INSTALLED ON THE GATE.
06/19/2009 VIOL - MEANS OF EGRESS Violation 2006 IFC 1027.3
REPAIR THE EXIT SIGNS BY THE SOUTH AND NORTH GATES ON THE NORTH BUILDING
06/19/2009 VIOL - MEANS OF EGRESS Violation REPAIR THE EMERGENCY LIGHTS BY THE SOUTH AND NORTH GATES ON THE NORTH BUILDING
06/19/2009 VIOL - MEANS OF EGRESS Violation 2006 IFC 1028.2
REPAIR STAIRS ON NORTH BUILDING ON FAR EAST END FROM 3RD FLOOR TO GROUND FLOOR. THE STAIRS ARE CURRENTLY UNSAFE ACCORDING TO AN ARCHITECT AND ARE BLOCKED.