Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/17/2009

Applicant:

STATE OF ARIZONA

Description:

Full Fire Prevention Inspection**** Olena Ulloa**** 622-1157

Outstanding Inspections

Case Number: T09FR01977
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
06/17/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. All open spaces located in the electrical panels shall be properly covered.
06/17/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Repair all deficiencies noted on the hood system inspection report.
06/17/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.3.5 Security grilles. In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles. _____1. The west security grill shall be locked in the open position when the building is occupied. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
06/17/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Replace the missing door handle for the west egress door.
06/17/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" above the west egress door and on the inside of the west security grill.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01977
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/24/2009 INSP - FULL GDAURIA Approved