Case: T09FR01941
Case Details
Entered Date:
06/12/2009
Applicant:
DE GRAVE INVESTMENTS LLC
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T09FR01941
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2009 | INSP - FULL | JNAGORE | Violation | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm)or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exit signs shall be illuminated at all times. |
06/12/2009 | INSP - FULL | JNAGORE | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Do not block electrical panels. |