Case: T09FR01941

Parcel: 12415008A


Addresses:

827 E 17TH ST


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR01941

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
06/12/2009 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Do not block electrical panels.
06/12/2009 INSP - FULL Violation 1011.1 Where required. Exits and exit access doors shall be
marked by an approved exit sign readily visible from any direction
of egress travel. Access to exits shall be marked by readily
visible exit signs in cases where the exit or the path of egress
travel is not immediately visible to the occupants. Exit sign
placement shall be such that no point in a corridor is more than
100 feet (30 480 mm)or the listed viewing distance for the sign,
whichever is less, from the nearest visible exit sign.
Exit signs shall be illuminated at all times.