Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR01786
Case Details
Entered Date:
05/26/2009
Applicant:
H L F PROPERTIES INC
Description:
Full Fire Prevention Inspection
Outstanding Inspections
Case Number: T09FR01786
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 05/26/2009 | VIOL - PRECAUTION AGAINST FIRE | DSIWARSKI | Violation | IFC.315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. ___Remove combustible boxes away from water heated. |
| 05/26/2009 | VIOL - FIRE PROTECTION SYSTEMS | DSIWARSKI | Violation | IFC.904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ___ Portable Class K fire extinguisher required. |
| 05/26/2009 | VIOL - FIRE PROTECTION SYSTEMS | DSIWARSKI | Violation | IFC.904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed and the required amount of agent verified. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer. ____Hood fire extinguishing system over due for inspection. TFC.904.11.7 All deep-fat fryers shall be installed with at least a 16 inch (406 mm) space between the fryer and surface flames of adjacent cooking appliances. Exception: When a steel or tempered glass baffle plate is installed at a minimum 8 inches (203 mm) in height between the fryer and surface flames of the adjacent cooking appliance, the requirement for a 16 inch space shall not apply. Where the fryer and the surface flames of the adjacent cooking appliance are at different horizontal planes, the minimum height of 8 inches (203 mm) shall be measured from the higher of the two. ____Install a 8 inch baffel between the fryer and surface flame. |