Description:

Peter Piper's Pizza fire inspection.

Outstanding Inspections

Case Number: T09FR01746
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
05/18/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
05/18/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
05/18/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. __ Sprinkler head inside walk-in cooler is being obstructed by light fixture.
05/18/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request.
05/18/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
05/18/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01746
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/04/2009 INSP - REINSPECTION JLOYA Approved All violations abated.