Case: T09FR01746

Parcel: 11904600E


Addresses:

3717 S 12TH AV


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01746

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
05/18/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request.
05/18/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern.
__ Sprinkler head inside walk-in cooler is being obstructed by light fixture.