Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/14/2009

Applicant:

STATE OF ARIZONA

Description:

Catalina house fire inspection.

Outstanding Inspections

Case Number: T09FR01700
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
05/14/2009 VIOL - FIRE SERVICE FEATURES JLOYA Violation TFC 508.5.4 - Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. ____ Clear storage from sprinkler room closet.
05/14/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels, remove all flammable liquids and combustible materials from 2nd floor electrical closet.
05/14/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. ___ Replace flexible cord going thru wall at sprinkler room.
05/14/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. __Provide copy of last sprinkler report.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01700
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/14/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
06/02/2009 INSP - REINSPECTION JLOYA Approved All violations abated.