Case: T09FR01700

Parcel: 11706214A


Addresses:

115 S 4TH AV


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR01700

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
05/14/2009 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact.
___ Replace flexible cord going thru wall at sprinkler room.
05/14/2009 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.
_____ Clear area around electrical panels, remove all flammable liquids and combustible materials from 2nd floor electrical closet.