Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. ___ Replace flexible cord going thru wall at sprinkler room. |
|
| 05/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels, remove all flammable liquids and combustible materials from 2nd floor electrical closet. |