Case: T09FR01657
Case Details
Entered Date:
05/12/2009
Applicant:
H L F PROPERTIES INC
Description:
Full Fire Prevention Inspection
Outstanding Inspections
Case Number: T09FR01657
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 05/12/2009 | VIOL - BUILDING SVCS & SYSTEMS | DSIWARSKI | Violation | IFC.605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. IFC.605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ____ Front Window extension cord shall not be used as permanent wireing. ____ Extension cord in Refrigerated Flower Display area must not be used as permanent wireing. ____ Extension cord in Back room shall not be used as permanent wireing. |
| 05/12/2009 | VIOL - MEANS OF EGRESS | DSIWARSKI | Violation | IFC.1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. IFC.1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted ____Remove flush bolt from rear door. IFC.1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,... ____Egress door must have sign that reads: " THIS DOOR IS TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". |
| 05/13/2009 | VIOL - COMPRESSED GASES | DSIWARSKI | Violation | IFC.3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in accordance with Sections 3003.5.1 through 3003.5.3. ____ Secure compressed gas cylinder in back room. |