Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T09FR01657
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC.605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. IFC.605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ____ Front Window extension cord shall not be used as permanent wireing. ____ Extension cord in Refrigerated Flower Display area must not be used as permanent wireing. ____ Extension cord in Back room shall not be used as permanent wireing. |