Case: T09FR01582
Case Details
Entered Date:
05/11/2009
Applicant:
DND NEFFSON CO
Description:
Full Fire Prevention Inspection Building Rep: Ilene Rosenheim Phone # 888-9218
Outstanding Inspections
Case Number: T09FR01582
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2009 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
05/11/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____ Remove the breaker inhibiters from your electrical box as they prevent the box from breaking properly and are deemed an electrical hazard |
05/11/2009 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Fix, repair, and/or replace all non-working exit signs in order to meet code standards (Back up power) ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ___________________ Passed on: ________ (Joseph P. Longo) |