Case: T09FR01582

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR01582

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/11/2009 VIOL - MEANS OF EGRESS Correction Required 1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

_____ Fix, repair, and/or replace all non-working exit signs in order to meet code standards (Back up power)