Case: T09FR01324
Case Details
Entered Date:
04/16/2009
Applicant:
248 S OCCIDENTAL BOULEVARD DE LLC 34.88% &
Description:
Hood System Complaint Venice Pizza Marry M. Weger Inspector M. Pursley
Outstanding Inspections
Case Number: T09FR01324
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2009 | INSP - FULL | RESSLING | Correction Required | (Copy of hood system report is in complaint log.) Exhaust fan shuts off when system is tripped. |
05/08/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPURSLEY | Correction Required | 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. ***NFPA 96*** 904.11.2 System interconnection. The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual. ____Hood ventilation should continue to run and all fuel and electric under hood system shall automatically shut off when system is activated ****1997 IFC 1006.2.4.1-Automatic shutoff**** Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____________________ ___/___/___ |
Completed Inspections
Case Status: FIELD
Case Number: T09FR01324
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2009 | COMPLIANCE | MPURSLEY | Approved | Chief Uthe OK'd fan. Fan interconnection was designed to code at time of insallation 5/20/09. |