Case: T09FR01324

Parcel: 13312006M

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01324

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/08/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required 904.1 General. Automatic fire-extinguishing systems, other
than automatic sprinkler systems, shall be designed, installed,
inspected, tested and maintained in accordance with the provisions
of this section and the applicable referenced standards. ***NFPA 96***

904.11.2 System interconnection. The actuation of the fire
extinguishing system shall automatically shut down the fuel
or electrical power supply to the cooking equipment. The
fuel and electrical supply reset shall be manual.

____Hood ventilation should continue to run and all fuel and electric under hood system shall automatically shut off when system is activated

****1997 IFC 1006.2.4.1-Automatic shutoff****

Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: _____________________ ___/___/___