Case: T09FR01218
Case Details
Entered Date:
04/08/2009
Applicant:
CROSSROAD PROPERTIES LLC
Description:
SPRINKLER INSPECTION
Outstanding Inspections
Case Number: T09FR01218
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2009 | INSP - NIGHT | EDESCHAI | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE CONTRACTORS REPAIR ORDER SHALL BE FORWARDED TO THIS OFFICE. 1) PROVIDE SWAY BRACING AT THE TOP OF THE SPRINKLER RISER 2) THE TOP PRESSURE GUAGE AT THE RISER SHALL BE REPLACED OR RECALIBRATED 3) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL INSPECTION |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01218
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2009 | INSP - FULL | EDESCHAI | Approved | CORRECTION REPORT TO SYSTEMS |