Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/08/2009

Applicant:

PARK MALL LLC

Description:

Full Inspection conducted 04/07/09 I have received a copy of this report and understand the corrections needed: ________________ Business Owner: Lilly Urias Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Re-inspection: __/__/__ (or after). Approved ________

Outstanding Inspections

Case Number: T09FR01214
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/08/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.3 - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
04/08/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.6 - Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____ Repair or remove damaged light fixture in stockroom.
04/08/2009 VIOL - MEANS OF EGRESS DGREENLE Violation TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear back hallway to the width of the exit door and maintain it this way at all times.
04/08/2009 VIOL - MEANS OF EGRESS DGREENLE Violation TFC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. _____ Relocate exit sign @ door from dressing rooms.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01214
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
04/08/2009 INSP - FULL DGREENLE Approved Certificate of Occupancy on file.
06/01/2009 INSP - REINSPECTION DGREENLE Approved corrections made but still need to maintain rear hallway egress width