Case: T09FR01096
Case Details
Entered Date:
03/27/2009
Applicant:
N/A
Description:
Full Fire Prevention Inspection. Jake Halifax 293-8100 Ext. 235
Outstanding Inspections
Case Number: T09FR01096
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2009 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | IFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____1. Remove all storage in the electrical room located in the "Suit's" area. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 03/27/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 604.1 Installation. Emergency and standby power systems required by this code or the International Building Code shall be installed in accordance with this code, NFPA110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval. _____1. Provide documentation of the testing and maintenance performed on the generator within the last year. |
| 03/27/2009 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1. Replace the missing ceiling tiles located in the "vision" closet. _____2. Repair the hole in the wall located in the "Shoe Annex". |
| 03/27/2009 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | IFC 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position. _____1. All fire doors located in the stock rooms shall close automatically. |
| 03/27/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Provide documentation of the current Fire alarm inspection performed. |
| 03/27/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. _____1. Mount the portable fire extinguisher located in the 2nd floor elevator room. _____2. Mount the portable fire extinguisher located in the "Office's" area. |
| 03/27/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____1. The "Suit's" EXIT corridor shall be illuminated. _____2. Repair or replace the broken lighting units located in the EXIT corridor on the first floor by the elevator. |
| 03/27/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. _____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." on the inside of the south entrance door. |
| 03/27/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1. Repair or replace the illuminated EXIT sign located in the shoe stock room. |
| 03/27/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove all merchandise from obstructing the EXIT door located in the "Children's" area. _____2. Remove all storage from the EXIT corridor located near the "Boy's" area. _____3. Repair the EXIT door located in "Suit's". NOTE: It will not open properly. _____4. Remove all storage from the EXIT corridor located near the "Dress's" area. _____5. Remove the display rack from obstructing the exit door located on the 1st floor in "Casual's". |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01096
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |