Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR01096
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. _____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." on the inside of the south entrance door. |
|
| 03/27/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove all merchandise from obstructing the EXIT door located in the "Children's" area. _____2. Remove all storage from the EXIT corridor located near the "Boy's" area. _____3. Repair the EXIT door located in "Suit's". NOTE: It will not open properly. _____4. Remove all storage from the EXIT corridor located near the "Dress's" area. _____5. Remove the display rack from obstructing the exit door located on the 1st floor in "Casual's". |
|
| 03/27/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____1. The "Suit's" EXIT corridor shall be illuminated. _____2. Repair or replace the broken lighting units located in the EXIT corridor on the first floor by the elevator. |
|
| 03/27/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1. Repair or replace the illuminated EXIT sign located in the shoe stock room. |