Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/09/2009

Applicant:

PDR INVESTORS LLC

Description:

99 cent store

Outstanding Inspections

Case Number: T09FR00845
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/09/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels
03/09/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
03/09/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
03/09/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
03/09/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
03/09/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
03/09/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
03/09/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width.
03/09/2009 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00845
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/24/2009 INSP - REINSPECTION JLOYA Approved All violations abated.