Case: T09FR00837
Case Details
Entered Date:
03/09/2009
Applicant:
ATRIA CAMPANA DEL RIO LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR00837
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 1.) TFC 906.7 THE PORTABLE FIRE EXTINGUISHER IN FRONT OFFICE MUST BE MOUNTED ON WALL BRACKET. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 10.) TFC 906.1 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN 3RD FLOOR STORGE ROOM BY "C" ELEVATOR NEEDS TO BE SEALED. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 2.) TFC 901.6 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN THE KITCHEN BY THE ICE MACHINE MUST BE SEALED. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 3.) TFC 901.6 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN THE KITCHEN STORAGE ROOM MUST BE SEALED. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 4.) TFC 901.6 TWO SPRINKLER HEADS HAVE A GAP AT THE CEILING IN THE POOL ROOM THAT MUST BE SEALED. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 5.) TFC 605.4 THE MULIT-PLUG ELECTRICAL ADAPTER IN THE HAIR SALON NEEDS TO BE REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 6.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT BY ROOM #217 NEEDS TO BE SERVICED/REPAIRED TO ILLUMINATE PRORERLY. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 7.) TFC 605.6 THE FLUORESCENT LIGHT FIXTURE IN THE 2ND FLOOR D-WING STORAGE ROOM NEEDS A COVER PLATE TO ENCLOSE OPEN WIRE SPLICES. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 8.) TFC 703.1.1 THE WALL PENETRATION BEHIND THE DOOR IN THE 2ND FLOOR D-WING REFUSE CLOSET MUST BE SEALED. |
03/09/2009 | INSP - FULL | RSPANGLE | Violation | 9.) TFC 906.1 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEONS IN SHOP MUST BE SEALED. |