Case: T09FR00729
Case Details
Entered Date:
02/23/2009
Applicant:
BARCLAY CRESWIN RETAIL LLC
Description:
Kids outlet fire inspection.
Outstanding Inspections
Case Number: T09FR00729
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
02/23/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___Remove keyed lock and sliding bolt mechanism from rear emergency exit , replace with approved locking mechanis. |
02/23/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles. Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00729
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |