Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/23/2009

Applicant:

BARCLAY CRESWIN RETAIL LLC

Description:

Kids outlet fire inspection.

Outstanding Inspections

Case Number: T09FR00729
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/23/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
02/23/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___Remove keyed lock and sliding bolt mechanism from rear emergency exit , replace with approved locking mechanis.
02/23/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles. Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00729
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/17/2009 INSP - REINSPECTION JLOYA Approved All violations abated.