Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

02/10/2009

Applicant:

RASMUSSEN NELS E JR TR

Description:

Caller states people are parking in front of gas meter would like to have gas company put stakes around meter, she stated that can only be done if TFD says it is a hazard please call Loren Rasmassen at 797-0304- or cell phone 907-0495

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00554
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 3
End Date Description Inspector Results Comments
02/12/2009 INSP - FULL JLOYA Approved Please provide vahicle impact protection for the gas meter located at the SW corner of the building , for your cooperation thank you. Inspector Jorg Loya 791-4502 ext 146.
02/12/2009 VIOL - PRECAUTION AGAINST FIRE JLOYA Approved 312.1 General. Vehicle impact protection required by this code shall be provided by posts that comply with Section 312.2 or by other approved physical barriers that comply with Section 312.3. 312.2 Posts. Guard posts shall comply with all of the following requirements: 1. Constructed of steel not less than 4 inches (102 mm) in diameter and concrete filled. 2. Spaced not more than 4 feet (1219 mm) between posts on center. 3. Set not less than 3 feet (914 mm) deep in a concrete footing of not less than a 15-inch (381 mm) diameter. 4. Set with the top of the posts not less than 3 feet (914 mm) above ground. 5. Located not less than 3 feet (914 mm) from the protected object.
03/03/2009 INSP - REINSPECTION JLOYA Approved Bollars in place.