Case: T09FR00554

Parcel: 12007351A


Addresses:

375 W AJO WY


Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T09FR00554

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2009 VIOL - PRECAUTION AGAINST FIRE Approved 312.1 General. Vehicle impact protection required by this
code shall be provided by posts that comply with Section 312.2
or by other approved physical barriers that comply with Section
312.3.
312.2 Posts. Guard posts shall comply with all of the following
requirements:
1. Constructed of steel not less than 4 inches (102 mm) in
diameter and concrete filled.
2. Spaced not more than 4 feet (1219 mm) between posts on
center.
3. Set not less than 3 feet (914 mm) deep in a concrete footing
of not less than a 15-inch (381 mm) diameter.
4. Set with the top of the posts not less than 3 feet (914 mm)
above ground.
5. Located not less than 3 feet (914 mm) from the protected
object.