Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T09FR00540
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
02/06/2009 INSP - FULL RSPANGLE Approved NOTE: THE BUILDING HAS A NEW FIRE ALARM SYSTEM INSTALLED. THE FINAL ACCEPTANCE TEST DONE IN JUNE OF 2008 IS ACCEPTABLE AS AN ANNUAL INSPECTION. FIRE DRILL RECORDS ARE IN COMPLIANCE.
02/06/2009 INSP - FULL RSPANGLE Approved 5.) TFC 901.6.2 THE ANNUAL SPRINKLER SYSTEM INSP. REPORT INCLUDING THE 5 YR. CHECK VALVE MUST BE SUBMITTED AT TIME OF RE-INSPECTION.
02/06/2009 INSP - FULL RSPANGLE Approved 4.) TFC 703.2.2 HOLD-OPEN AND AUTOMATIC DOOR CLOSERS, WHERE PROVIDED, SHALL BE MAINTAINED. H.R. AREA MUST HAVE DOOR CLOSERS IN PLACE. IN AREAS WITH SPRINKLER COVERAGE THIS REQUIREMENT CAN BE WAIVED.
02/06/2009 INSP - FULL RSPANGLE Approved 3.) TFC 703.1.1 IN H.R. HALLWAY THE CLOSET ACROSS FROM THE EDUCATION OFFICE THERE ARE CEILING PENETRATIONS THAT NEED TO BE SEALED.
02/06/2009 INSP - FULL RSPANGLE Approved 2.) TFC 901.6 SPRINKLER HEAD ESCUTCHEON IS MISSING IN THE 2ND THERAPY ROOM FROM ORTHO TREATMENT.
02/06/2009 INSP - FULL RSPANGLE Approved 1.) TFC 703.1.1 IN ADULT WEST, IN ELECTRICAL & aLARM SYSTEM CLOSET - SEAL AROUND ELECTRICAL CONDUIT IN THE CEILING.