Case: T09FR00540

Parcel: 110120910


Addresses:

2695 N CRAYCROFT RD


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR00540

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
02/06/2009 INSP - FULL Violation 1.) TFC 703.1.1 IN ADULT WEST, IN ELECTRICAL & aLARM SYSTEM CLOSET - SEAL AROUND ELECTRICAL CONDUIT IN THE CEILING.
02/06/2009 INSP - FULL Violation 2.) TFC 901.6 SPRINKLER HEAD ESCUTCHEON IS MISSING IN THE 2ND THERAPY ROOM FROM ORTHO TREATMENT.
02/06/2009 INSP - FULL Violation 3.) TFC 703.1.1 IN H.R. HALLWAY THE CLOSET ACROSS FROM THE EDUCATION OFFICE THERE ARE CEILING PENETRATIONS THAT NEED TO BE SEALED.
02/06/2009 INSP - FULL Violation 4.) TFC 703.2.2 HOLD-OPEN AND AUTOMATIC DOOR CLOSERS, WHERE PROVIDED, SHALL BE MAINTAINED. H.R. AREA MUST HAVE DOOR CLOSERS IN PLACE. IN AREAS WITH SPRINKLER COVERAGE THIS REQUIREMENT CAN BE WAIVED.
02/06/2009 INSP - FULL Violation 5.) TFC 901.6.2 THE ANNUAL SPRINKLER SYSTEM INSP. REPORT INCLUDING THE 5 YR. CHECK VALVE MUST BE SUBMITTED AT TIME OF RE-INSPECTION.
02/06/2009 INSP - FULL Approved NOTE: THE BUILDING HAS A NEW FIRE ALARM SYSTEM INSTALLED. THE FINAL ACCEPTANCE TEST DONE IN JUNE OF 2008 IS ACCEPTABLE AS AN ANNUAL INSPECTION.

FIRE DRILL RECORDS ARE IN COMPLIANCE.