Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T09FR00540
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2009 | INSP - FULL | Violation | 1.) TFC 703.1.1 IN ADULT WEST, IN ELECTRICAL & aLARM SYSTEM CLOSET - SEAL AROUND ELECTRICAL CONDUIT IN THE CEILING. | |
02/06/2009 | INSP - FULL | Violation | 2.) TFC 901.6 SPRINKLER HEAD ESCUTCHEON IS MISSING IN THE 2ND THERAPY ROOM FROM ORTHO TREATMENT. | |
02/06/2009 | INSP - FULL | Violation | 3.) TFC 703.1.1 IN H.R. HALLWAY THE CLOSET ACROSS FROM THE EDUCATION OFFICE THERE ARE CEILING PENETRATIONS THAT NEED TO BE SEALED. | |
02/06/2009 | INSP - FULL | Violation | 4.) TFC 703.2.2 HOLD-OPEN AND AUTOMATIC DOOR CLOSERS, WHERE PROVIDED, SHALL BE MAINTAINED. H.R. AREA MUST HAVE DOOR CLOSERS IN PLACE. IN AREAS WITH SPRINKLER COVERAGE THIS REQUIREMENT CAN BE WAIVED. | |
02/06/2009 | INSP - FULL | Violation | 5.) TFC 901.6.2 THE ANNUAL SPRINKLER SYSTEM INSP. REPORT INCLUDING THE 5 YR. CHECK VALVE MUST BE SUBMITTED AT TIME OF RE-INSPECTION. | |
02/06/2009 | INSP - FULL | Approved | NOTE: THE BUILDING HAS A NEW FIRE ALARM SYSTEM INSTALLED. THE FINAL ACCEPTANCE TEST DONE IN JUNE OF 2008 IS ACCEPTABLE AS AN ANNUAL INSPECTION. FIRE DRILL RECORDS ARE IN COMPLIANCE. |